Project Description

ZigBee Modbus Energy Meter 3~ / 6~ Print datasheet

Bidirectional power meters for monitoring one three phase line / three single phase lines or two three phase lines / six single phase lines, for installation in a ZigBee wireless device network.
Main technical specifications
  • ZigBee wireless power and energy meter
  • For monitoring one three phase line or three single phase lines (ZR-HM3-xx-EM)
  • For monitoring two three phase lines or six single phase lines (ZR-HM6-xx-EM)
  • Mono-directional Active / Reactive Energy Meter Log
  • Instant bidirectional measurement of active and reactive power
  • Current transformers for currents of 50 A, 100 A or 200 A max included
  • Router function within the ZigBee wireless network
  • External antenna
Applications
  • Building automation and industrial control systems
  • Energy monitoring and management
Description

Wireless energy meter for measuring electrical consumption in civil, industrial and service applications. Data is acquired by split core current transformers (TA).

The device measures voltage, current, instant power and energy consumption.

Thanks to continuous power, the device can also function as a ZigBee signal repeater and as a parent device for battery powered sensors.

Connection diagram
Models available
Image Code Description
ZR-HM3-xx-xx-01 ZR-HM3-50-EM
ZR-HM3-100-EM
ZR-HM3-200-EM
Energy Meter 3~ for 1 three phase line or 3 single phase lines, 50 A
Energy Meter 3~ for 1 three phase line or 3 single phase lines, 100 A
Energy Meter 3~ for 1 three phase line or 3 single phase lines, 200 A
ZR-HM6-xx-xx-01 ZR-HM6-50-EM
ZR-HM6-100-EM
ZR-HM6-200-EM
Energy Meter 6~ for 2 three phase lines or 6 single phase lines, 50 A
Energy Meter 6~ for 2 three phase lines or 6 single phase lines, 100 A
Energy Meter 6~ for 2 three phase lines or 6 single phase lines, 200 A
Technical specifications
General specifications Chip Ember EM3587
Compatible IEEE 802.15.4
Stack EmberZnet 5.3.1 (ZigBee PRO)
Modbus / RTU
Radio specifications Frequency: 2405 MHz to 2480 MHz
Modulation: DSSS
Nominal transmission power: 10 mW (10 dBm)
Receiver sensitivity: 103 dBm
Antenna External antenna with 5 dB gain
Radio range: 50 m outdoor; 20 m indoor
Antenna connector RP-SMA connector
Power supply 230 Vac 1.5 W 50 to 60 Hz
Max measured current ZR-HMx-50-EM: 50 A max per phase
ZR-HMx-100-EM: 100 A max per phase
ZR-HMx-200-EM: 200 A max per phase
Status display 6x LED indicator
Measurements Voltage (V), Current (A), PowerFactor,
Bidirectional active power [W], Reactive power [VAr], Apparent power [VA], Active energy [Wh], Reactive energy [VArh]
Connections Screw terminals (5.08 mm pitch)
Inputs 2x non-isolated inputs for voltage-free contacts
Closing current 0.01 mA. Use self-cleaning contacts
ZR-HM3-XX-EM: 3x inputs for measurement with TA
ZR-HM6-XX-EM: 6x inputs for measurement with TA
Digital outputs 1x auxiliary relay, 230 Vac 10A max (pure resistive)
Current Transformers ZR-HMx-50-EM: 50 A max; diameter 15 mm
ZR-HMx-100-EM: 100 A max diameter 15 mm
ZR-HMx-200-EM: 200 A max diameter 25 mm
Mounting DIN rail
Ambient parameters Operating conditions: -0 to +50 °C; <80% R.H. n. c.
Storage conditions: -20 to +70 °C; <80% R.H. n. c.
Degree of protection IP20
Insulation Class II
Conformity Directives 2014/53/EU (RED) 2011/65/EU (RoHS) 2012/19/EU (WEEE) 1999/519/EC
ETSI EN 300 328; ETSI EN 301 489-1; ETSI EN 301 489-17; EN 61326-1; EN 61010-1; EN 62479
Dimensions (L x H x D) 105 x 110 x 60 mm
Weight 330 g